If pulling 24 amps through a TT-30 or 40 amps through a 14-50 trips a breaker, then it's the host's fault for the campground having a shoddy electrical system, not the truck driver's fault.
[–] arrowleaf 1 day ago
Lol in what world? Campgrounds routinely have next to no funding, if they even have power pedestals I wouldn't expect them to be wired for anything more than an RV.
[–] josephcsible 1 day ago
The entire reason we have so many different types of receptacles is so to keep you from plugging in something that the circuit can't handle. They shouldn't be giving people 14-50's if they don't have 50A peak and 40A continuous available. (There is a code exception to only allow 40A peak/32A continuous to a 14-50, but that's all most portable EV chargers draw anyway, so I doubt it even met that. And TT-30 offers no such exception at all.)
[–] hnav 1 day ago
Since the whole campground went dark, presumably it was the main breaker. The branch circuit must be sized to the outlet type, but the total rating of all branch circuits usually exceeds the main breaker rating.
[–] josephcsible 1 day ago
That would be a reasonable explanation if most of the campsites had people charging EVs at their max individual current, but it sounded like just one did.
[–] rootusrootus 1 day ago
[–] colejohnson66 1 day ago
[–] rootusrootus 1 day ago
Also, a bog standard 14-50 is likely not suited for 80% steady EV usage anyway. They make EV-rated 14-50s now because people keep melting the older ones. And that happens even though the vast majority of chargers won't draw more than 32A on a 14-50 due to the historical popularity of using 40A breakers for a 14-50 receptacle.